RFD-200 S3 Digital Timer.
The RFD-200 S3 is a portable relay test set that delivers performance verification testing of electromechanical, electronic, and microprocessor-based protective relays in their operating installations. The RFD-200 S3 is a rugged test set suitable for testing a variety of protection relays operated in both indoor and outdoor environments. The unit¡¯s ergonomic design and intuitive control panel layout make it ideal for first-time users who have little or no training.
Technical Specifications
TYPE | Portable relay test set | |||||||||||||||||||||||||
INPUT POWER | 100 – 120 Vac or 200 – 240 Vac (factory pre-set), 50/60 Hz | |||||||||||||||||||||||||
PHYSICAL SPECIFICATIONS | 17¡±W x 12.5¡±H x 12¡±D, (42.7 cm x 32.0 cm x 30.5 cm); Weight: 35 lbs (15.9 kg) | |||||||||||||||||||||||||
AMPERE METER INPUT RANGES | Internal input range: 0 – 250 A; Accuracy: 2% of reading ¡¾ 10 mA, External AC input range: 0 – 6A; Accuracy: 1% of reading ¡¾ 10mA External DC input range: 0 – 6A; Accuracy: 0.5% of reading ¡¾1 count Measurement Method: True RMS for AC | |||||||||||||||||||||||||
VOLT METER INPUT RANGE | 0 – 600.0V; AC accuracy: 1% of reading ¡¾1 count; DC accuracy 0.5% of reading ¡¾1 count Measurement Method: True RMS for AC | |||||||||||||||||||||||||
AUXILIARY POWER SUPPLIES | 24 Vdc @ 1 A, 48 Vdc @ 0.25 A, 124 Vdc @ 0.125 A | |||||||||||||||||||||||||
POWER RESISTORS | 5 ¥Ø/50 W, 1 ¥Ø/50 W, 25 ¥Ø/50 W, 100 ¥Ø/50 W, 500 ¥Ø/50 W | |||||||||||||||||||||||||
SAFETY | Designed to meet IEC61010 (1995), UL61010A-1, CSA-C22.2 standards | |||||||||||||||||||||||||
ENVIRONMENT | Operating: -10¢ªC to 50¢ª C (15¢ªF to +122¢ª F); Storage: -30¢ª C to 70¢ª C (-22¢ªF to +158¢ª F) | |||||||||||||||||||||||||
OPTIONS | Transportation case | |||||||||||||||||||||||||
WARRANTY | One year on parts and labor | |||||||||||||||||||||||||
AC Current Output | ||||||||||||||||||||||||||
| ||||||||||||||||||||||||||
AC Voltage Output | ||||||||||||||||||||||||||
| ||||||||||||||||||||||||||
DC Voltage Output | ||||||||||||||||||||||||||
| ||||||||||||||||||||||||||
RFD-200 Timer Second Display In seconds and cycles (50/60 Hz programmable) | ||||||||||||||||||||||||||
| ||||||||||||||||||||||||||
Timer Cycles Display | ||||||||||||||||||||||||||
| ||||||||||||||||||||||||||
Specifications are valid at nominal voltage and ambient temperature of +25¢ªC (+77¢ªF). |
Cable | Part Number |
---|---|
[8000-0016] Power + Ground Combination Cable | 8000-0016 |
[8000-0078] RFD-200 Cable Set | 8000-0078 |